Quiz-summary
0 of 10 questions completed
Questions:
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
Information
Premium Practice Questions
You have already completed the quiz before. Hence you can not start it again.
Quiz is loading...
You must sign in or sign up to start the quiz.
You have to finish following quiz, to start this quiz:
Results
0 of 10 questions answered correctly
Your time:
Time has elapsed
Categories
- Not categorized 0%
Unlock Your Full Report
You missed {missed_count} questions. Enter your email to see exactly which ones you got wrong and read the detailed explanations.
Submit to instantly unlock detailed explanations for every question.
Success! Your results are now unlocked. You can see the correct answers and detailed explanations below.
- 1
- 2
- 3
- 4
- 5
- 6
- 7
- 8
- 9
- 10
- Answered
- Review
-
Question 1 of 10
1. Question
What best practice should guide the application of Primary power sources (AC power)? During the installation of a new fire alarm control unit in a commercial facility, a technician must ensure the primary power supply is configured to maximize system reliability and meet standard safety requirements. Which configuration and identification method is required for the branch circuit supplying the system?
Correct
Correct: According to NFPA 72, the primary power for a fire alarm system must be supplied by a dedicated branch circuit. This ensures that the system is not affected by faults in other equipment. Furthermore, the circuit must be clearly identified at the breaker (usually with a red marking) and must be mechanically protected (locked in the ‘on’ position) to prevent accidental or unauthorized disconnection of power to the life safety system.
Incorrect: Sharing the circuit with other loads like emergency lighting is prohibited because a fault in the lighting system could trip the breaker and disable the fire alarm. Using GFCI protection is generally discouraged for fire alarm primary power because nuisance tripping could lead to the system running on battery power unnecessarily. Leaving the breaker unlocked or accessible to unauthorized personnel is a violation of the requirement for mechanical protection, which is intended to prevent the system from being powered down unintentionally.
Takeaway: Primary power for fire alarm systems must be a dedicated, labeled, and mechanically locked branch circuit to ensure continuous system operation and prevent accidental de-energization.
Incorrect
Correct: According to NFPA 72, the primary power for a fire alarm system must be supplied by a dedicated branch circuit. This ensures that the system is not affected by faults in other equipment. Furthermore, the circuit must be clearly identified at the breaker (usually with a red marking) and must be mechanically protected (locked in the ‘on’ position) to prevent accidental or unauthorized disconnection of power to the life safety system.
Incorrect: Sharing the circuit with other loads like emergency lighting is prohibited because a fault in the lighting system could trip the breaker and disable the fire alarm. Using GFCI protection is generally discouraged for fire alarm primary power because nuisance tripping could lead to the system running on battery power unnecessarily. Leaving the breaker unlocked or accessible to unauthorized personnel is a violation of the requirement for mechanical protection, which is intended to prevent the system from being powered down unintentionally.
Takeaway: Primary power for fire alarm systems must be a dedicated, labeled, and mechanically locked branch circuit to ensure continuous system operation and prevent accidental de-energization.
-
Question 2 of 10
2. Question
An internal review at a credit union examining Manual pull stations as part of complaints handling has uncovered that several devices installed during a 2022 renovation are positioned in a way that hinders immediate access. Specifically, one station in the main lobby is mounted 54 inches above the finished floor, and another is located 10 feet from the required exit door. According to NFPA 72 standards for initiating devices, what is the primary corrective action required for these manual pull stations to ensure compliance with life safety objectives?
Correct
Correct: Relocating the stations ensures the operable part is between 42 and 48 inches from the floor and within 5 feet of the exit doorway, which aligns with NFPA 72 requirements for accessibility and prompt emergency initiation.
Incorrect: Installing a protective cover does not resolve the height or distance violations. Adding a second station at a lower height while leaving the non-compliant one is not a recognized corrective measure for installation errors. Replacing manual stations with automatic detectors is generally not allowed as a substitute for required manual initiation points in a fire alarm system design.
Takeaway: Manual pull stations must be mounted between 42 and 48 inches high and within 5 feet of exit doors to comply with NFPA 72 accessibility and life safety standards.
Incorrect
Correct: Relocating the stations ensures the operable part is between 42 and 48 inches from the floor and within 5 feet of the exit doorway, which aligns with NFPA 72 requirements for accessibility and prompt emergency initiation.
Incorrect: Installing a protective cover does not resolve the height or distance violations. Adding a second station at a lower height while leaving the non-compliant one is not a recognized corrective measure for installation errors. Replacing manual stations with automatic detectors is generally not allowed as a substitute for required manual initiation points in a fire alarm system design.
Takeaway: Manual pull stations must be mounted between 42 and 48 inches high and within 5 feet of exit doors to comply with NFPA 72 accessibility and life safety standards.
-
Question 3 of 10
3. Question
An escalation from the front office at a private bank concerns Cable types and ratings during record-keeping. The team reports that during a recent renovation of the bank’s data storage wing, a technician is reviewing the installation of fire alarm circuits within a vertical shaft that connects three floors. The project documentation indicates that the cable used is marked as FPLR. The lead inspector is questioning whether this cable meets the requirements for this specific installation environment. Which of the following statements correctly identifies the application and rating of the FPLR cable in this scenario?
Correct
Correct: FPLR stands for Fire Power-Limited Riser cable. According to NFPA 70 (National Electrical Code), riser-rated cables are specifically tested for fire-spread characteristics to prevent fire from traveling between floors via vertical shafts. It is the appropriate choice for a vertical run in a shaft that is not part of a plenum system.
Incorrect: The description of a cable designed for environmental air-handling spaces refers to FPLP (Plenum) rated cable, not FPLR. The claim that FPLR is only for horizontal runs is incorrect, as its primary designation is for vertical (riser) applications. The suggestion that FPLR is limited to residential use is false, as it is a standard commercial grade cable for multi-story buildings.
Takeaway: FPLR cable is specifically rated for vertical riser applications to prevent the spread of fire between floors but cannot be used in plenum spaces without a higher rating (FPLP).
Incorrect
Correct: FPLR stands for Fire Power-Limited Riser cable. According to NFPA 70 (National Electrical Code), riser-rated cables are specifically tested for fire-spread characteristics to prevent fire from traveling between floors via vertical shafts. It is the appropriate choice for a vertical run in a shaft that is not part of a plenum system.
Incorrect: The description of a cable designed for environmental air-handling spaces refers to FPLP (Plenum) rated cable, not FPLR. The claim that FPLR is only for horizontal runs is incorrect, as its primary designation is for vertical (riser) applications. The suggestion that FPLR is limited to residential use is false, as it is a standard commercial grade cable for multi-story buildings.
Takeaway: FPLR cable is specifically rated for vertical riser applications to prevent the spread of fire between floors but cannot be used in plenum spaces without a higher rating (FPLP).
-
Question 4 of 10
4. Question
During a routine supervisory engagement with a mid-sized retail bank, the authority asks about Strobes (visual notification appliances) in the context of client suitability. They observe that several visual notification appliances installed in a large, open-plan banking hall are flashing independently rather than in unison. When evaluating the risk and compliance of this installation, the internal auditor must identify the primary life safety objective for requiring synchronization of these devices when multiple strobes are visible from a single location.
Correct
Correct: Synchronization is a critical safety requirement defined in NFPA 72. When multiple strobes flash at different rates within the same field of vision, the composite flash rate can exceed the threshold (typically 2 flashes per second) known to trigger seizures in people with photosensitive epilepsy. Ensuring all devices flash at the same time prevents this physiological hazard.
Incorrect: While circuit loading and voltage drop are important engineering considerations for system functionality, they are managed through wire sizing and power supply calculations rather than flash timing. Increasing light intensity is achieved by selecting the correct candela rating for the specific room dimensions, not by timing the flashes. Monitoring circuit integrity is achieved through the use of end-of-line resistors and supervisory current, which is independent of whether the devices are synchronized.
Takeaway: Strobe synchronization is a mandatory life safety feature designed to prevent the triggering of photosensitive epileptic seizures when multiple appliances are in the field of view.
Incorrect
Correct: Synchronization is a critical safety requirement defined in NFPA 72. When multiple strobes flash at different rates within the same field of vision, the composite flash rate can exceed the threshold (typically 2 flashes per second) known to trigger seizures in people with photosensitive epilepsy. Ensuring all devices flash at the same time prevents this physiological hazard.
Incorrect: While circuit loading and voltage drop are important engineering considerations for system functionality, they are managed through wire sizing and power supply calculations rather than flash timing. Increasing light intensity is achieved by selecting the correct candela rating for the specific room dimensions, not by timing the flashes. Monitoring circuit integrity is achieved through the use of end-of-line resistors and supervisory current, which is independent of whether the devices are synchronized.
Takeaway: Strobe synchronization is a mandatory life safety feature designed to prevent the triggering of photosensitive epileptic seizures when multiple appliances are in the field of view.
-
Question 5 of 10
5. Question
A whistleblower report received by a listed company alleges issues with Speaker systems for voice evacuation during incident response. The allegation claims that during a recent quarterly maintenance inspection, the fire alarm system failed to detect a disconnected speaker in a remote stairwell. As an auditor reviewing the life safety system’s compliance with NFPA 72 standards, which of the following conditions represents the most critical failure in the system’s design or maintenance?
Correct
Correct: In accordance with NFPA 72, fire alarm notification appliance circuits, including those for speakers, must be supervised for integrity. This ensures that if a device is removed or a wire is broken, the fire alarm control unit (FACU) will receive and display a trouble signal. A failure to detect a disconnected speaker indicates a lack of supervision, which is a fundamental life safety requirement to ensure the system is operational when needed.
Incorrect: Using a pre-recorded voice is a standard and acceptable practice for voice evacuation systems and does not constitute a failure. Achieving a sound pressure level of 15 decibels above the average ambient noise level is the standard requirement for public mode notification, not a deficiency. Sizing backup batteries for 24 hours of standby followed by 15 minutes of alarm is the standard requirement for emergency voice/alarm communications systems (EVACS).
Takeaway: Supervision of notification appliance circuits is a mandatory requirement to ensure the integrity of the fire alarm system and the immediate detection of faults or disconnected devices.
Incorrect
Correct: In accordance with NFPA 72, fire alarm notification appliance circuits, including those for speakers, must be supervised for integrity. This ensures that if a device is removed or a wire is broken, the fire alarm control unit (FACU) will receive and display a trouble signal. A failure to detect a disconnected speaker indicates a lack of supervision, which is a fundamental life safety requirement to ensure the system is operational when needed.
Incorrect: Using a pre-recorded voice is a standard and acceptable practice for voice evacuation systems and does not constitute a failure. Achieving a sound pressure level of 15 decibels above the average ambient noise level is the standard requirement for public mode notification, not a deficiency. Sizing backup batteries for 24 hours of standby followed by 15 minutes of alarm is the standard requirement for emergency voice/alarm communications systems (EVACS).
Takeaway: Supervision of notification appliance circuits is a mandatory requirement to ensure the integrity of the fire alarm system and the immediate detection of faults or disconnected devices.
-
Question 6 of 10
6. Question
What is the most precise interpretation of Pull box and junction box requirements for NICET Fire Alarm Systems Level I (FAS I)? During a site walkthrough of a commercial facility, an inspector examines the installation of the fire alarm system’s field wiring. The inspector notes several junction boxes located in the plenum space above a drop-ceiling. According to NFPA 72 and the National Electrical Code (NEC), which requirement must be met regarding the identification and accessibility of these boxes?
Correct
Correct: According to NFPA 72 and the NEC (NFPA 70), fire alarm circuits must be identified at all terminal and junction locations to prevent accidental interference with the system during maintenance of other building utilities. Additionally, all junction and pull boxes must be accessible, meaning they can be reached for maintenance or inspection without necessitating the removal of any permanent part of the building structure.
Incorrect: While painting boxes red is a common industry practice, the code specifically requires ‘identification’ rather than a specific color like red. There is no specific height requirement of 18 inches above a ceiling grid for these boxes. All junction boxes in a fire alarm system require identification, not just those with active components, to ensure the entire circuit path is known. Plenum spaces require specific box types (plenum-rated), but they do not require hermetic sealing or specialized permits for standard maintenance access.
Takeaway: Fire alarm junction boxes must be clearly identified and remain accessible to ensure system integrity and facilitate safe maintenance and troubleshooting.
Incorrect
Correct: According to NFPA 72 and the NEC (NFPA 70), fire alarm circuits must be identified at all terminal and junction locations to prevent accidental interference with the system during maintenance of other building utilities. Additionally, all junction and pull boxes must be accessible, meaning they can be reached for maintenance or inspection without necessitating the removal of any permanent part of the building structure.
Incorrect: While painting boxes red is a common industry practice, the code specifically requires ‘identification’ rather than a specific color like red. There is no specific height requirement of 18 inches above a ceiling grid for these boxes. All junction boxes in a fire alarm system require identification, not just those with active components, to ensure the entire circuit path is known. Plenum spaces require specific box types (plenum-rated), but they do not require hermetic sealing or specialized permits for standard maintenance access.
Takeaway: Fire alarm junction boxes must be clearly identified and remain accessible to ensure system integrity and facilitate safe maintenance and troubleshooting.
-
Question 7 of 10
7. Question
When operationalizing Sprinkler system integration with fire alarm systems, what is the recommended method for ensuring that the closure of a sprinkler control valve is properly monitored by the fire alarm control unit?
Correct
Correct: According to NFPA 72 and NFPA 13 standards, supervisory signal-initiating devices (tamper switches) must be used to monitor the position of control valves. These devices are required to transmit a supervisory signal if the valve is moved from its normal position within two revolutions of the handwheel or one-fifth of the total travel distance. This ensures the fire alarm system can identify when the sprinkler system is impaired without triggering a full fire alarm.
Incorrect: Connecting a tamper switch to a notification appliance circuit is incorrect because supervisory conditions should not initiate a general building evacuation. Treating a valve closure as a fire alarm signal is incorrect because it would cause a false fire alarm and unnecessary emergency response for a maintenance condition. Waterflow switches are designed to detect the flow of water resulting from a sprinkler head activation or a pipe burst, not to monitor the mechanical position of a control valve.
Takeaway: Sprinkler control valves must be monitored by supervisory initiating devices that signal a change in valve position within specific mechanical limits to ensure system readiness.
Incorrect
Correct: According to NFPA 72 and NFPA 13 standards, supervisory signal-initiating devices (tamper switches) must be used to monitor the position of control valves. These devices are required to transmit a supervisory signal if the valve is moved from its normal position within two revolutions of the handwheel or one-fifth of the total travel distance. This ensures the fire alarm system can identify when the sprinkler system is impaired without triggering a full fire alarm.
Incorrect: Connecting a tamper switch to a notification appliance circuit is incorrect because supervisory conditions should not initiate a general building evacuation. Treating a valve closure as a fire alarm signal is incorrect because it would cause a false fire alarm and unnecessary emergency response for a maintenance condition. Waterflow switches are designed to detect the flow of water resulting from a sprinkler head activation or a pipe burst, not to monitor the mechanical position of a control valve.
Takeaway: Sprinkler control valves must be monitored by supervisory initiating devices that signal a change in valve position within specific mechanical limits to ensure system readiness.
-
Question 8 of 10
8. Question
When evaluating options for Tamper switches on valves, what criteria should take precedence to ensure the system meets NFPA 72 requirements for supervisory signal initiation during the installation of a new sprinkler monitoring system?
Correct
Correct: According to NFPA 72 and NFPA 13, supervisory switches (tamper switches) on valves must be installed such that they trigger a supervisory signal if the valve is moved from its normal position. The specific requirement is that the signal must be initiated within the first two revolutions of the handwheel or within one-fifth of the total travel distance of the valve apparatus. This ensures that the fire alarm system is alerted to a potentially closed water supply before the valve is fully shut.
Incorrect: Initiating a waterflow alarm is incorrect because valve tampering is a supervisory condition, not an actual fire or waterflow event; these signals must be distinct. Wiring the tamper switch in series with a waterflow switch is a violation of monitoring standards as it would prevent the system from identifying which specific device was activated and could disable alarm reporting. Local-only notification is insufficient because the fire alarm control unit and the supervising station must be notified of any condition that affects the integrity of the fire protection system.
Takeaway: Valve tamper switches must initiate a distinct supervisory signal within two revolutions or one-fifth of the valve’s travel to ensure the fire suppression water supply is monitored for availability.
Incorrect
Correct: According to NFPA 72 and NFPA 13, supervisory switches (tamper switches) on valves must be installed such that they trigger a supervisory signal if the valve is moved from its normal position. The specific requirement is that the signal must be initiated within the first two revolutions of the handwheel or within one-fifth of the total travel distance of the valve apparatus. This ensures that the fire alarm system is alerted to a potentially closed water supply before the valve is fully shut.
Incorrect: Initiating a waterflow alarm is incorrect because valve tampering is a supervisory condition, not an actual fire or waterflow event; these signals must be distinct. Wiring the tamper switch in series with a waterflow switch is a violation of monitoring standards as it would prevent the system from identifying which specific device was activated and could disable alarm reporting. Local-only notification is insufficient because the fire alarm control unit and the supervising station must be notified of any condition that affects the integrity of the fire protection system.
Takeaway: Valve tamper switches must initiate a distinct supervisory signal within two revolutions or one-fifth of the valve’s travel to ensure the fire suppression water supply is monitored for availability.
-
Question 9 of 10
9. Question
Which safeguard provides the strongest protection when dealing with Class X wiring configurations? A technician is tasked with ensuring a signaling line circuit (SLC) in a high-occupancy facility meets the performance requirements for Class X as defined by NFPA 72. The system must remain fully operational, including the ability to report an alarm, even when subjected to a single wire-to-wire short circuit.
Correct
Correct: Class X circuits (formerly Style 7) are specifically designed to be fault-tolerant against opens, ground faults, and short circuits. To maintain functionality during a short circuit, isolation modules must be used. These modules detect the short and disconnect the affected segment of the loop, allowing the fire alarm control unit to continue communicating with the remaining devices from both directions of the redundant loop path.
Incorrect: Using end-of-line resistors is characteristic of Class B circuits for supervision but does not provide short-circuit protection for an SLC. T-tap configurations are generally prohibited in Class X wiring because they do not support the required redundant loop return path to the panel. While shielded cabling may reduce interference, it does not provide the mechanical or electrical bypass capability required to survive a direct wire-to-wire short circuit.
Takeaway: The defining characteristic of Class X wiring is its ability to maintain full communication during a short circuit, which is achieved through the use of isolation modules.
Incorrect
Correct: Class X circuits (formerly Style 7) are specifically designed to be fault-tolerant against opens, ground faults, and short circuits. To maintain functionality during a short circuit, isolation modules must be used. These modules detect the short and disconnect the affected segment of the loop, allowing the fire alarm control unit to continue communicating with the remaining devices from both directions of the redundant loop path.
Incorrect: Using end-of-line resistors is characteristic of Class B circuits for supervision but does not provide short-circuit protection for an SLC. T-tap configurations are generally prohibited in Class X wiring because they do not support the required redundant loop return path to the panel. While shielded cabling may reduce interference, it does not provide the mechanical or electrical bypass capability required to survive a direct wire-to-wire short circuit.
Takeaway: The defining characteristic of Class X wiring is its ability to maintain full communication during a short circuit, which is achieved through the use of isolation modules.
-
Question 10 of 10
10. Question
Working as the compliance officer for a credit union, you encounter a situation involving Multi-criteria/multi-sensor smoke detectors during complaints handling. Upon examining an internal audit finding, you discover that several branch locations are experiencing high rates of nuisance alarms in breakroom areas. The audit recommends replacing existing single-sensor photoelectric detectors with multi-criteria detectors to improve system reliability. When evaluating this recommendation, which characteristic of multi-criteria detectors is most relevant to reducing these unwanted alarms?
Correct
Correct: Multi-criteria detectors are designed to reduce nuisance alarms by using sophisticated internal algorithms to analyze data from multiple sensors (such as photoelectric, thermal, or carbon monoxide). By requiring a specific combination or signature of fire-related phenomena, the detector can effectively differentiate between a real fire and common nuisance sources like steam or localized cooking smoke.
Incorrect: Increasing sensitivity during business hours would likely increase the frequency of nuisance alarms rather than reduce them. Manual override switches on detector heads are not a standard or permitted feature for fire alarm initiation devices as they compromise life safety. Configuring sensors to operate independently without integrated logic describes a basic multi-sensor arrangement that would actually increase the probability of false alarms, as any one sensor could trigger the system.
Takeaway: Multi-criteria detectors utilize integrated algorithms to analyze multiple fire signatures, which significantly reduces nuisance alarms in environments prone to non-fire triggers like breakrooms or kitchens-adjacent areas.
Incorrect
Correct: Multi-criteria detectors are designed to reduce nuisance alarms by using sophisticated internal algorithms to analyze data from multiple sensors (such as photoelectric, thermal, or carbon monoxide). By requiring a specific combination or signature of fire-related phenomena, the detector can effectively differentiate between a real fire and common nuisance sources like steam or localized cooking smoke.
Incorrect: Increasing sensitivity during business hours would likely increase the frequency of nuisance alarms rather than reduce them. Manual override switches on detector heads are not a standard or permitted feature for fire alarm initiation devices as they compromise life safety. Configuring sensors to operate independently without integrated logic describes a basic multi-sensor arrangement that would actually increase the probability of false alarms, as any one sensor could trigger the system.
Takeaway: Multi-criteria detectors utilize integrated algorithms to analyze multiple fire signatures, which significantly reduces nuisance alarms in environments prone to non-fire triggers like breakrooms or kitchens-adjacent areas.